Technical guide
Are Reconditioned Circuit Breakers Any Good?
Yes — if "reconditioned" means what it should. Here is what a properly reconditioned ACB or MCCB has had done to it, the evidence you should be given, and the three questions that separate a rebuilt breaker from a cleaned one.
The word "reconditioned" covers everything from a full strip-down with new contacts and an injection test to a wipe with a rag and a new label. Buyers know this, which is why the question gets asked. The answer is that a properly reconditioned breaker meets the duty its switchboard was designed around, and a badly reconditioned one is a fault waiting for load. The difference is entirely in what was done and what was recorded.
What "reconditioned" should mean
- Full strip-down, not a surface clean. Arc chutes off, mechanism out, contacts exposed.
- Every wearing component measured against the manufacturer's limit and replaced where it fails: main and arcing contacts, contact springs, arc chute plates, latches, pivots, coils, the charging motor.
- Mechanism degreased and re-lubricated with the specified grade. This one item is the difference between a breaker that closes cleanly for fifteen years and one that seizes in five.
- Trip unit tested by secondary injection across every element against the published curve — and replaced if out of tolerance.
- Contact resistance and insulation resistance measured and recorded per pole.
- Operated through its full sequence electrically and mechanically, including anti-pumping, undervoltage and auxiliaries.
In the US the PEARL reconditioning standard formalises this; in the UK there is no equivalent badge, so the supplier's own test record has to do the work.
The evidence you should be given
A test certificate against the breaker's serial number, showing the trip unit settings during test, pick-up and trip time for each protection element, contact resistance per pole, insulation resistance, and the instrument used. A parts list saying what was replaced and where the parts came from — OEM, donor stock or re-manufactured. Photographs of the strip-down. And a warranty with a term on it. A reconditioned breaker sold without these is a used breaker with a price premium.
Three questions to ask
- "Can I see the injection test results?" Not "was it tested" — the numbers. If they aren't offered, the test wasn't done or wasn't recorded, and either way you can't prove the protection works.
- "What was replaced?" A reconditioned ACB with no parts replaced has been cleaned. That can be legitimate for a low-hours unit, but the contact measurements should be on the certificate to show why.
- "What is the warranty, and who honours it?" Twelve months is the norm for a genuine rebuild. A thirty-day warranty is a returns policy.
When reconditioned beats new
Obsolete ranges are the obvious case: a reconditioned Masterpact M, first-generation Emax or Moeller IZM fits the cell the new range won't, and avoids a board project. Lead time is the other: a reconditioned unit from stock is on site in days when the OEM quotes weeks. And for a fleet — a data hall, a wind farm, a hospital estate — a pool of reconditioned exchange units on the shelf is what turns a breaker failure from an outage into a swap.
We recondition the customer's own breaker and return it with the certificate described above; our sister company Replacement Circuit Breakers holds tested units for sale. Either way, the test record comes with the breaker. Refurbishment, in detail.
Get started
Tell us about the breaker
Make, model and rating from the nameplate, plus a description of the fault. We'll come back with a clear recommendation and a fixed price — usually the same working day.
- Workshop & office01977 253063
- Out of hours07496 013884
- Email & photosinfo@circuitbreakerrepair.co.uk
- WorkshopUnit 13–17 Dale Court, Pontefract, West Yorkshire WF9 3FL