Workshop: Mon–Fri 8am–5pm · Pontefract, West Yorkshire · UK-wide Out of hours: 07496 013884

Wind energy · Contactors

Wind Turbine Generator Contactor Overhaul

The stator, rotor and crowbar contactors in a turbine converter cabinet cycle on every start and stop. We overhaul the big frames — Schneider LC1F, ABB AF and A-series, Siemens 3RT and 3TF — to OEM wear limits, and test every one for pick-up, drop-out and contact resistance before it goes back.

  • Frames265 – 2100 A
  • ScopeContacts · coils · poles · chutes
  • TestingPick-up, drop-out, mΩ per pole
  • Warranty12 months

The problem

A contactor rated for a million operations gets there quickly in a turbine

The generator contactor connects the stator to the grid when the turbine reaches synchronous speed and drops out on every stop — grid event, high wind cut-out, curtailment, maintenance. The rotor-side and crowbar contactors in a doubly-fed machine work harder still, switching under the converter's control during ride-through. A frame that would last decades in a motor control centre is worn out in a few years of turbine duty.

What wears is well understood. Main contacts erode and pit until contact resistance climbs and the poles run hot. Springs lose pressure. Coils overheat in a cabinet that spends summer afternoons above 40 °C. Arc chutes crack and their splitters erode. Magnet faces pick up debris and the contactor chatters. Auxiliary blocks — which the controller relies on for feedback — fail intermittently long before the main poles do.

Overhauling the contactor addresses all of it at once, on a unit whose mounting, terminations and control wiring already match the cabinet. The alternative is a new contactor, which for the older frames means an OEM lead time and, often, a different footprint.

Six restored contactor pole assemblies with new silver contact tips and copper carriers
Contactor pole assemblies after overhaul — new tips, clean carriers
Overhaul scope — high-current contactors
Main contactsReplaced as complete sets — fixed and moving — with new contact springs; pressure verified
Pole assembliesCarriers inspected for heat distortion and cracking; replaced from donor stock where needed
Arc chutesInspected for cracking, splitter erosion and tracking; cleaned or replaced
Coil & magnetCoil resistance and insulation tested; magnet faces cleaned and checked for shading-ring damage; coil replaced where marginal
AuxiliariesAuxiliary contact blocks and interlocks tested and replaced — these are cheap and fail first
TerminationsMain terminals inspected for heat damage; re-plated or replaced
TestPick-up and drop-out voltage, contact resistance per pole, insulation resistance, mechanical operation, coil current

Ranges

Contactor families in the turbine converter cabinet

Schneider TeSys LC1F

The 265 to 2100 A frames used as generator and crowbar contactors across a large part of the European-built fleet. Contact kits, coils, pole carriers and auxiliary blocks — a range we overhaul continuously, including for US customers.

LC1F265 · F330 · F400 · F500 · F630 · F780 · F800 · F1250

ABB AF and A-series

AF-series electronically controlled coils and the older A-series AC-coil frames. The AF coil electronics fail on supply transients; the A-series suffer classic magnet and shading-ring wear. Both are rebuilt.

AF265 – AF2650 · A260 – A300 · EK / EH series

Siemens 3RT and 3TF

3RT1 and 3RT2 frames on newer machines; 3TF6 on the older fleet. Contact sets, coils and arc chute assemblies, plus the 3RH auxiliary blocks that feed the controller.

3RT1075 – 3RT1476 · 3TF68 / 3TF69

Testing

What "tested" means for a contactor

A contactor that closes when you press it is not a tested contactor. Every overhauled unit is proved on the bench for the things that actually take a turbine off: pick-up voltage at the bottom of the coil's tolerance band, so it closes reliably when the control supply sags; drop-out voltage, so it releases when commanded and holds when it shouldn't; contact resistance measured per pole with a micro-ohmmeter, so the poles will run cool at full generator current; coil current and insulation resistance; and mechanical operation for chatter and bounce. Auxiliary contacts are proved in every position.

The results go on the certificate against the unit's serial number. Fit it, connect it, and the controller sees exactly what it saw with the original.

Test record — per contactor
Pick-up voltageMeasured; must close at or below the lower coil tolerance limit
Drop-out voltageMeasured; must release within the manufacturer's band
Contact resistanceμΩ / mΩ per pole at test current; balanced across poles
Insulation resistancePole-to-pole and pole-to-earth
CoilResistance and operating current at rated voltage
AuxiliariesEvery NO/NC block proved in both positions

FAQs

Frequently asked

Is it worth overhauling a contactor rather than fitting a new one?

For the large frames, yes — the overhaul costs a fraction of a new unit and the OEM lead time on a 1250 A contactor is not something you want a turbine waiting on. For small frames in the pitch and yaw systems, a new contactor is often the right answer and we'll say so.

The contactor chatters or hums. Repairable?

Almost always. Chatter comes from debris or corrosion on the magnet faces, a damaged shading ring, a weak coil or a low control supply. The first three are overhaul items; the last is a site fault we'll help you identify from the pick-up voltage measurement.

Can you supply just the contact kit?

Yes, where we hold it. But a contact kit fitted to a contactor with tired springs, a marginal coil and worn auxiliaries is a short-term fix. We'd rather overhaul the unit and certify it — the labour difference is small.

Do you do the fitting?

The overhaul is workshop work. Removal and refitting is usually done by your technicians on the same climb; where you want us in the tower, we attend.

Get started

Tell us about the breaker

Make, model and rating from the nameplate, plus a description of the fault. We'll come back with a clear recommendation and a fixed price — usually the same working day.

Photos help us quote faster — email pictures of the breaker and its nameplate to info@circuitbreakerrepair.co.uk with your name, or reply to our confirmation.

We reply the same working day. Site down? Call 01977 253063 — out of hours 07496 013884.

Call an engineer Get a quote